The sprinklers are on but no-one’s home. Bathla has been ordered to fix defects at its Kembla Grange development. Photo: Region.
The NSW Building Commission has ordered embattled property developer Bathla to rectify serious faults at its Kembla Grange housing development.
Bathla entered into voluntary administration on 25 August with $3.3 billion in debts.
Administrators Teneo have been trying to secure funding from private lenders to pay the company’s 350 staff and finish its 45 construction projects.
Universal Property Group is the parent entity of the group and is responsible for the construction of 108 units in five buildings at 141 Darkes Road.
Work started in August 2021 but buyers have been left in limbo while completion dates have been pushed further and further back.
On Thursday (3 September) the Building Commission served a building work rectification order and a prohibition notice, which means an occupation certificate cannot be issued for the development until the rectification order is revoked by the commission.
The commission can give an order to a developer if it has a “reasonable belief” that: the building work was or is carried out in a manner that could result in a serious defect in relation to a residential apartment building, or a residential apartment building has a serious defect.
Department officers inspected the building on 8 July and the resultant inspection report detailed a series of defects relating to waterproofing, fire safety, structural systems and building essential services.
The commission has identified 12 serious defects which must be rectified.

Bathla’s sign on the fence of the development. Photo: Region.
Inspectors found that waterproofing around the basement did not follow approved plans and a non-compliant installation of a waterproofing system could allow water in, which could cause “unhealthy or dangerous conditions, loss of amenity for occupants and undue dampness or deterioration of building elements”.
The fire pump room mechanical ventilation system had not been installed in accordance with the approved mechanical plans, which the inspectors say could adversely affect the operation and may impede the fire brigade and delay the suppression of a fire.
The sprinkler installation is not in accordance with the approved wet fire design drawings, the defect list continued, and a number of fire-rated doors between the basement and the exit stair had deteriorated, with visible delamination and warping of the door leaves. “The deterioration appears to have resulted from exposure to weather and moisture,” the order said.
Further, inspectors observed that the required bush fire protection measures have not been completed in accordance with the approved bush fire assessment report.
Two of the defects relate to the structural systems.
“General poor execution of various structural elements was observed,” the order said.
“Joints were packed with dirt and debris on the ground.
“In the slab soffit the joint seal is damaged and there are remnants of rotten timber pieces embedded there.
“There is polystyrene left behind (textured yellowish material) that was not properly removed, cleaned and filled with structural grout. The concrete edge of the rectangular recess shows fractured edges and concrete spalling leaving behind weak concrete zones.
“The failure to rectify structural elements might not withstand the combination offloads and other actions to which it may be reasonably subjected in its design life, can cause economic loss and environmental damage.”
The company has eight months to rectify the defects, or it could face criminal penalties.